SETPOINT OUTPUT TIME-OUT
COUNTER AUTO RESET
SPn tOUt ?
? 001.00
0.01
to
599.99
seconds
SPn AUtO
?
?
NO
NO
@2Ero-Str
2Ero-End
CtLd-Str
CtLd-End
This parameter is only active if the Setpoint Action is set to time out ( t-OUt ).
Enter the value in seconds that the Setpoint output will be active, once the
Setpoint Value is reached.
SETPOINT VALUE
This parameter automatically resets the counter to which the setpoint is
assigned ( SPn ASN ) each time the setpoint value is reached. The automatic reset
can occur at output start, or at output end if the Setpoint Output Action is
programmed for timed output mode. The Reset-to-Count Load selections
(“ CtLd- ”) only apply to Counter A assignment. This reset may be different from
the Counter A Reset Action selected in Module 1.
SPn VAL ?
? 00000100
Count A:
Count B:
Rate:
- 9999999 to 99999999
0 to 9999999
0 to 999999
SELECTION ACTION
NO No Auto Reset.
2Ero-Str Reset to Zero at the start of output activation.
CtLd-End Reset to out only). Load value at the end of output activation
?
SP1 OFF2 ?
?
SP2 OFF1 ?
?
Enter  the  desired  Setpoint  value.  To  enter  a  negative  setpoint  value,
increment digit 8 to display a “-” sign (Counter A only).
SETPOINT OUTPUT LOGIC
SPn OUt ?
NOr rEV
NOr
Normal ( NOr ) turns the output “on” when activated and “off” when
deactivated. Reverse ( rEV ) turns the output “off” when activated and “on” when
deactivated.
SETPOINT ANNUNCIATOR
SPn LIt ? NOr                rEV
? NOr
Normal ( NOr ) displays the setpoint annunciator when the corresponding
output is “on”. Reverse ( rEV ) displays the setpoint annunciator when the output
is “off”.
SETPOINT OUTPUT POWER-UP STATE
CtLd-Str Reset to Count Load value at the start of output activation.
2Ero-End Reset to Zero at the end of output activation (timed out only).
Count
(timed
SETPOINT 1 OUTPUT OFF AT SETPOINT 2 (SP1 Only)
NO Out2-Str Out2-End
NO
This parameter will deactivate Setpoint 1 output at the Start or End of
Setpoint 2 output (O1 off at O2). The “ -End ” setting only applies if Setpoint 2
Output Action is programmed for timed output.
SETPOINT 2 OUTPUT OFF AT SETPOINT 1 (SP2 Only)
NO Out1-Str Out1-End
NO
This parameter will deactivate Setpoint 2 output at the Start or End of
Setpoint 1 output (O2 off at O1). The “ -End ” setting only applies if Setpoint 1
Output Action is programmed for timed output.
SPn P-UP
?
OFF
ON
SAVE
SETPOINT OUTPUT RESET WITH MANUAL RESET
?
?
SPn StbY ?
?
? OFF
SAVE will restore the output to the same state it was at before the meter was
powered down. ON will activate the output at power up. OFF will deactivate the
output at power up.
SETPOINT BOUNDARY TYPE
SPn tYPE ? HI-ACt          LO-ACt
? HI-ACt
High Acting Boundary Type activates the output when the assigned display
value ( SPn ASN ) equals or exceeds the Setpoint value. Low Acting activates the
output when the assigned display value is less than or equal to the Setpoint.
SETPOINT STANDBY OPERATION
NO YES
NO
This parameter only applies to Low Acting Boundary Type setpoints. Select
YES to disable a Low Acting Setpoint at power-up, until the assigned display
value crosses into the output “off” area. Once in the output “off” area, the
Setpoint will then function per the description for Low Acting Boundary Type.
12
SPn rSt ?
YES NO
YES
Selecting YES causes the Setpoint output to deactivate (reset) when the
Setpoint Assigned Counter is reset. The counter reset can occur by the RST
button, User Input, Counter Reset at Power-up or a serial Reset Counter
command.
This output reset will not occur when the Assigned Counter is reset by a
Setpoint generated Counter Auto Reset.
CHANGE DISPLAY COLOR WITH OUTPUT STATE
SPn ChC ?
NO YES
NO
This parameter enables the backlight CUB5 to switch the backlight color when
the output state changes. This parameter is only active for the backlight version.
相关PDF资料
P51-50-A-J-P-5V-000-000 SENSOR 50PSI 3/8-24 UNF 1-5V
P51-15-A-J-P-5V-000-000 SENSOR 15PSI 3/8-24 UNF 1-5V
CUB5R000 COUNTER/RATE IND DUAL REFL DISPL
P51-750-A-I-P-5V-000-000 SENSOR 750PSI 7/16-20 UNF 1-5V
ASFLMPC-48.000MHZ-Z-T OSC 48.000 MHZ CMOS MEMS SMD
P51-500-A-I-P-5V-000-000 SENSOR 500PSI 7/16-20 UNF 1-5V
P51-300-A-I-P-5V-000-000 SENSOR 300PSI 7/16-20 UNF 1-5V
P51-200-A-I-P-5V-000-000 SENSOR 200PSI 7/16-20 UNF 1-5V
相关代理商/技术参数
CUB5B000 CAL D 制造商:Red Lion Controls 功能描述:CALIBRATED W/DATA - Multifunction Counter, No. of Digits / Alpha:8, Digit Height
CUB5COM1 功能描述:RS485 SERIAL COMMO CARD RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030
CUB5COM2 功能描述:RS232 SERIAL COMM CARD FOR CUB5 RoHS:是 类别:工业控制,仪表 >> 配件 系列:* 标准包装:1 系列:Aero-Motive® 130117 附件类型:拖车带 适用于相关产品:标准盒式跟踪系统 其它名称:WM6183
CUB5IB00 功能描述:DC METER RED/GREEN BKLT RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030
CUB5IB00 CALIBRATED 制造商:Red Lion Controls 功能描述:DIGITAL PANEL METER MODEL CUB5 WITH CERTIFICATE OF CALIBRATION
CUB5IR00 功能描述:DC METER REFLECTIVE DISP RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030
CUB5OEMS 制造商:Red Lion Controls 功能描述:PROGRAMMING KIT FOR SOFTWARE
CUB5PB00 功能描述:PROCESS METER RED/GREEN BKLT RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030